// CODE SNIPPET

R702.7 Vapor Retarders

Residential Code 2015 of Utah > 7 Wall Covering > R702 INTERIOR COVERING > R702.7 Vapor Retarders
JUMP TO FULL CODE CHAPTER
Class I or II vapor retarders are required on the interior side of frame walls in Climate Zones 5, 6, 7, 8 and Marine 4.

Exceptions:

1. Basement walls.

2. Below-grade portion of any wall.

3. Construction where moisture or its freezing will not damage the materials.

R702.7.1 Class III Vapor Retarders

Class III vapor retarders shall be permitted where any one of the conditions in Table R702.7.1 is met.

TABLE R702.7.1 CLASS III VAPOR RETARDERS

CLIMATE
ZONE
CLASS III VAPOR RETARDERS PERMITTED FOR:a
Marine
4
Vented cladding over wood structural panels.
Vented cladding over fiberboard.
Vented cladding over gypsum.
Continuous insulation with R-value ≥ 2.5 over 2 × 4 wall.
Continuous insulation with R-value ≥ 3.75 over 2 × 6 wall.
5 Vented cladding over wood structural panels.
Vented cladding over fiberboard.
Vented cladding over gypsum.
Continuous insulation with R-value ≥ 5 over 2 × 4 wall.
Continuous insulation with R-value ≥ 7.5 over 2 × 6 wall.
6 Vented cladding over fiberboard.
Vented cladding over gypsum.
Continuous insulation with R-value ≥ 7.5 over 2 × 4 wall.
Continuous insulation with R-value ≥ 11.25 over 2 × 6 wall.
7 and 8 Continuous insulation with R-value ≥ 10 over 2 × 4 wall.
Continuous insulation with R-value ≥ 15 over 2 × 6 wall.

For SI: 1 pound per cubic foot = 16 kg/m3.
a. Spray foam with a maximum permeance of 1.5 perms at the installed thickness, applied to the interior cavity side of wood structural panels, fiberboard, insulating sheathing or gypsum is deemed to meet the continuous insulation requirement where the spray foam R-value meets or exceeds the specified continuous insulation R-value.

R702.7.2 Material Vapor Retarder Class

The vapor retarder class shall be based on the manufacturer's certified testing or a tested assembly.

The following shall be deemed to meet the class specified:

Class I: Sheet polyethylene, unperforated aluminum foil.

Class II: Kraft-faced fiberglass batts.

Class III: Latex or enamel paint.

R702.7.3 Minimum Clear Airspaces and Vented Openings for Vented Cladding

For the purposes of this section, vented cladding shall include the following minimum clear airspaces. Other openings with the equivalent vent area shall be permitted.

1. Vinyl lap or horizontal aluminum siding applied over a weather-resistive barrier as specified in Table R703.3(1).

2. Brick veneer with a clear airspace as specified in Table R703.8.4.

3. Other approved vented claddings.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1404.3 Exterior Walls, Vapor retarders
Vapor retarders as described in Section 1404.3.3 shall be provided in accordance with Sections 1404.3.1 and 1404.3.2, or an approved design using ...
Building Code 2018 of Utah > 14 Exterior Walls > 1404 Installation of Wall Coverings > 1404.3 Vapor retarders
1405.3 Exterior Walls, Vapor Retarders
Vapor retarders as described in Section 1405.3.3 shall be provided in accordance with Sections 1405.3.1 and 1405.3.2, or an approved design using ...
Building Code 2015 of Utah > 14 Exterior Walls > 1405 Installation of Wall Coverings > 1405.3 Vapor Retarders
604.11 Duct Systems, Vapor retarders
Where ducts used for cooling are externally insulated, the insulation shall be covered with a vapor retarder having a maximum permeance of 0.05 perm ...
Mechanical Code 2018 of Utah > 6 Duct Systems > 604 Insulation > 604.11 Vapor retarders
604.11 Duct Systems, Vapor Retarders
Where ducts used for cooling are externally insulated, the insulation shall be covered with a vapor retarder having a maximum permeance of 0.05 perm ...
Mechanical Code 2015 of Utah > 6 Duct Systems > 604 Insulation > 604.11 Vapor Retarders
R702.7 Wall Covering, Vapor Retarders
Class I or II vapor retarders are required on the interior side of frame walls in Climate Zones 5, 6, 7, 8 and Marine 4. Exceptions: 1 ...
Residential Code 2015 of Utah > 7 Wall Covering > R702 INTERIOR COVERING > R702.7 Vapor Retarders
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US