Shutoff valves shall be of an approved type; shall be constructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table G2420.1.1.

TABLE G2420.1.1 (409.1.1)
MANUAL GAS VALVE STANDARDS
VALVE STANDARDS APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1/2 psig PRESSURE OTHER VALVE APPLICATIONS
UP TO 1/2 psig PRESSURE UP TO 2 psig PRESSURE UP TO 5 psig PRESSURE UP TO 125 psig PRESSURE
ANSI Z21.15/CSA 9.1 X
ASME B16.44 X X Xa Xb
ASME B16.33 X X X X X
For SI: 1 pound per square inch gauge = 6.895 kPa.
  1. If labeled 2G.
  2. If labeled 5G.