5806.4.8 Vacuum Jacket Construction
JUMP TO FULL CODE CHAPTER
The vacuum jacket shall be designed and constructed in accordance with Section VIII of ASME Boiler and Pressure Vessel Code and shall be designed to withstand the anticipated loading, including loading from vehicular traffic, where applicable. Portions of the vacuum jacket installed below grade shall be designed to withstand anticipated soil, seismic and hydrostatic loading.
The vacuum jacket shall be protected by approved or listed corrosion-resistant materials or an engineered cathodic protection system. Where cathodic protection is utilized, an approved maintenance schedule shall be established. Exposed components shall be inspected not less than twice a year. Records of maintenance and inspection events shall be maintained.
An approved method shall be provided to indicate loss of vacuum within the vacuum jacket(s).
Related Code Sections
5806.4.8 Flammable Gases and Flammable Cryogenic Fluids, Vacuum Jacket Construction
The vacuum jacket shall be designed and constructed in accordance with Section VIII of ASME Boiler and Pressure Vessel Code and shall be designed ...
Fire Code 2021 of Colorado > 58 Flammable Gases and Flammable Cryogenic Fluids > 5806 Flammable Cryogenic Fluids > 5806.4 Underground Tanks for Liquid Hydrogen > 5806.4.8 Vacuum Jacket Construction
5806.4.8 Flammable Gases and Flammable Cryogenic Fluids, Vacuum Jacket Construction
The vacuum jacket shall be designed and constructed in accordance with Section VIII of ASME Boiler and Pressure Vessel Code and shall be designed ...
Fire Code 2018 of Colorado > 58 Flammable Gases and Flammable Cryogenic Fluids > 5806 Flammable Cryogenic Fluids > 5806.4 Underground Tanks for Liquid Hydrogen > 5806.4.8 Vacuum Jacket Construction
5806.4.8.2 Flammable Gases and Flammable Cryogenic Fluids, Corrosion Protection
The vacuum jacket shall be protected by approved or listed corrosion-resistant materials or an engineered cathodic protection system. Where ...
Fire Code 2018 of Colorado > 58 Flammable Gases and Flammable Cryogenic Fluids > 5806 Flammable Cryogenic Fluids > 5806.4 Underground Tanks for Liquid Hydrogen > 5806.4.8 Vacuum Jacket Construction > 5806.4.8.2 Corrosion Protection
5806.3.2 Flammable Gases and Flammable Cryogenic Fluids, Construction of the Vacuum Jacket (Outer Vessel)
The vacuum jacket used as an outer vessel for storage tanks in liquid hydrogen service shall be of welded steel construction designed to withstand ...
Fire Code 2021 of Colorado > 58 Flammable Gases and Flammable Cryogenic Fluids > 5806 Flammable Cryogenic Fluids > 5806.3 Above-Ground Tanks for Liquid Hydrogen > 5806.3.2 Construction of the Vacuum Jacket (Outer Vessel)
5806.3.2 Flammable Gases and Flammable Cryogenic Fluids, Construction of the Vacuum Jacket (Outer Vessel)
The vacuum jacket used as an outer vessel for storage tanks in liquid hydrogen service shall be of welded steel construction designed to withstand ...
Fire Code 2018 of Colorado > 58 Flammable Gases and Flammable Cryogenic Fluids > 5806 Flammable Cryogenic Fluids > 5806.3 Above-Ground Tanks for Liquid Hydrogen > 5806.3.2 Construction of the Vacuum Jacket (Outer Vessel)