362.12 Uses Not Permitted
JUMP TO FULL CODE CHAPTER
ENT shall not be used in the following:
- In any hazardous (classified) location, except as permitted by other articles in this Code
- For the support of luminaires and other equipment
- Where subject to ambient temperatures in excess of 50°C (122°F) unless listed otherwise
- For direct earth burial
- In exposed locations, except as permitted by 362.10(1), 362.10(5), and 362.10(7)
- In theaters and similar locations, except as provided in 518.4 and 520.5
- Where exposed to the direct rays of the sun, unless identified as sunlight resistant
- Where subject to physical damage
Informational Note: Extreme cold may cause some types of nonmetallic conduits to become brittle and therefore more susceptible to damage from physical contact.
Related Code Sections
242.40 Wiring and Protection, Uses Not Permitted
A surge arrester shall not be installed where the rating of the surge arrester is less than the maximum continuous phase-to-ground voltage ...
National Electrical Code 2020 of Minnesota > 2 Wiring and Protection > 242 Overvoltage Protection > 242.40 Uses Not Permitted
320.12 Wiring Methods and Materials, Uses Not Permitted
Type AC cable shall not be used as follows: Where subject to physical damage In damp or wet locations In air voids of masonry block or tile ...
National Electrical Code 2020 of Minnesota > 3 Wiring Methods and Materials > 320 Armored Cable: Type AC > 320.12 Uses Not Permitted
322.12 Wiring Methods and Materials, Uses Not Permitted
Flat cable assemblies shall not be used as follows: Where exposed to corrosive conditions, unless suitable for the application In hoistways ...
National Electrical Code 2020 of Minnesota > 3 Wiring Methods and Materials > 322 Flat Cable Assemblies: Type FC > 322.12 Uses Not Permitted
324.12 Wiring Methods and Materials, Uses Not Permitted
FCC systems shall not be used in the following locations: Outdoors or in wet locations Where subject to corrosive vapors In any hazardous ...
National Electrical Code 2020 of Minnesota > 3 Wiring Methods and Materials > 324 Flat Conductor Cable: Type FCC > 324.12 Uses Not Permitted
326.12 Wiring Methods and Materials, Uses Not Permitted
Type IGS cable shall not be used as interior wiring or be exposed in contact with buildings ...
National Electrical Code 2020 of Minnesota > 3 Wiring Methods and Materials > 326 Integrated Gas Spacer Cable: Type IGS > 326.12 Uses Not Permitted