1312.3 Use of Gas Hose Connectors
JUMP TO FULL CODE CHAPTER
Listed gas hose connectors shall be used in accordance with the manufacturer's installation instructions and in accordance with Section 1312.3.1 or Section 1312.3.2. [NFPA 54:9.6.2]
Indoor gas hose connectors shall be used only to connect laboratory, shop, and ironing appliances requiring mobility during operation and installed in accordance with the following:
- An appliance shutoff valve shall be installed where the connector is attached to the building piping.
- The connector shall be of minimum length and shall not exceed 6 feet (1829 mm).
- The connector shall not be concealed and shall not extend from one room to another or pass through wall partitions, ceilings, or floors. [NFPA 54:9.6.2(1)]
Where outdoor gas hose connectors are used to connect portable outdoor appliances, the connector shall be listed in accordance with CSA Z21.54 and installed in accordance with the following:
- An appliance shutoff valve, a listed quick-disconnect device, or a listed gas convenience outlet shall be installed where the connector is attached to the supply piping and in such a manner so as to prevent the accumulation of water or foreign matter.
- This connection shall be made only in the outdoor area where the appliance is to be used. [NFPA 54:9.6.2(2)]
- The connector length shall not exceed 15 feet (4572 mm).
Related Code Sections
1312.3 Fuel Gas Piping, Use of Gas Hose Connectors
Listed gas hose connectors shall be used in accordance with the manufacturer's installation instructions and in accordance with Section 1312.3.1 ...
Uniform Mechanical Code 2018 of Nevada > 13 Fuel Gas Piping > 1312.0 Appliance Connections to Building Piping > 1312.3 Use of Gas Hose Connectors
1212.3 Fuel Gas Piping, Use of Nonmetallic Gas Hose Connectors
)] Where outdoor gas hose connectors are used to connect portable outdoor appliances, the connector shall be listed in accordance ...
Uniform Plumbing Code 2018 of Nevada > 12 Fuel Gas Piping > 1212.0 Appliance and Equipment Connections to Building Piping > 1212.3 Use of Nonmetallic Gas Hose Connectors
1212.1 Fuel Gas Piping, Connecting Appliances and Equipment
gas hose connectors in accordance with Section 1212.3.
Unlisted gas hose connectors for use in laboratories and educational facilities in accordance ...
Uniform Plumbing Code 2018 of Nevada > 12 Fuel Gas Piping > 1212.0 Appliance and Equipment Connections to Building Piping > 1212.1 Connecting Appliances and Equipment
1312.0 Fuel Gas Piping, Appliance Connections to Building Piping
gas hose connectors in accordance with Section 1312.3.
Unlisted gas hose connectors for use in laboratories and educational facilities in accordance ...
Uniform Mechanical Code 2018 of Nevada > 13 Fuel Gas Piping > 1312.0 Appliance Connections to Building Piping
1212.0 Fuel Gas Piping, Appliance and Equipment Connections to Building Piping
gas hose connectors in accordance with Section 1212.3.
Unlisted gas hose connectors for use in laboratories and educational facilities in accordance ...
Uniform Plumbing Code 2018 of Nevada > 12 Fuel Gas Piping > 1212.0 Appliance and Equipment Connections to Building Piping