516.6 Use and Maintenance
JUMP TO FULL CODE CHAPTER
Automatic or manual covers on cooking appliances, especially fryers, shall not interfere with the application of the fire suppression system. [NFPA 96:13.6.1]
Filters shall be cleaned or replaced in accordance with the manufacturer's instructions. [NFPA 96:13.6.2]
ESPs shall be cleaned a minimum of once per week and in accordance with the manufacturer's instructions. [NFPA 96:13.6.3]
Inspection and testing of the total operation and safety interlocks in accordance with the manufacturer's instructions shall be performed by qualified service personnel not less than once every 6 months, or more frequently where required. [NFPA 96:13.6.5]
Fire-extinguishing equipment shall be inspected in accordance with Section 514.2. [NFPA 96:13.6.6]
A signed and dated log of maintenance as performed in accordance with Section 516.6.3 and Section 516.6.4 shall be available on the premises for use by the Authority Having Jurisdiction. [NFPA 96:13.6.7]
Related Code Sections
516.6 Exhaust Systems, Use and Maintenance
:13.6.6] A signed and dated log of maintenance ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.6 Use and Maintenance
516.6.5 Exhaust Systems, Inspection
Fire-extinguishing equipment shall be inspected in accordance with Section 514.2. [NFPA 96:13.6.6 ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.6 Use and Maintenance > 516.6.5 Inspection
102.2 Administration, Existing Installations
Mechanical systems lawfully in existence at the time of the adoption of this code shall be permitted to have their use, maintenance, or repair ...
Uniform Mechanical Code 2018 of Nevada > 1 Administration > 102.0 Applicability > 102.2 Existing Installations
102.2 Administration, Existing Installations
Plumbing systems lawfully in existence at the time of the adoption of this code shall be permitted to have their use, maintenance, or repair ...
Uniform Plumbing Code 2018 of Nevada > 1 Administration > 102.0 Applicability > 102.2 Existing Installations