605.1 General
Urinals shall comply with 605.
Advisory 605.1 General.  Stall-type urinals provide greater accessibility for a broader range of persons, including people of short stature.
605.2 Height and Depth
Urinals shall be the stall-type or the wall-hung type with the rim 17 inches (430 mm) maximum above the finish floor or ground.  Urinals shall be 13 1/2 inches (345 mm) deep minimum measured from the outer face of the urinal rim to the back of the fixture.
Figure 605.2 Height and Depth of Urinals
Figure (a) is an elevation drawing of a wall hung type having the urinal rim 17 inches (430 mm) maximum above the floor with a minimum depth of 13 1/2 inches (350 mm) measured from the outer face of the rim to the back of the fixture.  Figure (b) is an elevation drawing of a stall (floor) type having a minimum depth of 13 1/2 inches (350 mm) measured from the outer face of the rim to the back of the fixture.
605.3 Clear Floor Space
A clear floor or ground space complying with 305 positioned for forward approach shall be provided.
605.4 Flush Controls
Flush controls shall be hand operated or automatic.  Hand operated flush controls shall comply with 309.

Related Code Sections

605 Plumbing Elements and Facilities, Urinals
Urinals shall comply with 605. Advisory 605.1 General.  Stall-type urinals provide greater accessibility for a broader range of persons ...
213.3 Scoping Requirements, Plumbing Fixtures and Accessories
where six or more toilet compartments are provided, or where the combination of urinals and water closets totals six or more fixtures. Advisory ...
213.3.1 Scoping Requirements, Toilet Compartments
of urinals and water closets totals six or more fixtures. Advisory 213.3.1 Toilet Compartments.  A toilet compartment is a partitioned space ...
213 Scoping Requirements, Toilet Facilities and Bathing Facilities
Unisex toilet rooms shall contain not more than one lavatory, and two water closets without urinals or one water closet and one urinal.  Unisex ...