// CODE SNIPPET
511.1.1 Upblast Fans
JUMP TO FULL CODE CHAPTER
Upblast fans with motors surrounded by the airstream shall be hinged and supplied with flexible weatherproof electrical cable, and service hold-open retainers. Installation shall comply with the requirements of Section 510.9. Upblast fans shall have a drain directed to a readily accessible and visible grease receptacle not to exceed 1 gallon (4 L). [NFPA 96:8.1.2]
Related Code Sections
511.1.1 Exhaust Systems, Upblast Fans
Upblast fans with motors surrounded by the airstream shall be hinged and supplied with flexible weatherproof electrical cable, and service hold-open ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 511.0 Air Movement > 511.1 Exhaust Fans for Commercial Cooking Operations > 511.1.1 Upblast Fans
510.9.1 Exhaust Systems, Rooftop Terminations
with Section 507.4.8.
A hinged upblast fan supplied with flexible weatherproof electrical cable and service hold-open retainer to permit inspection ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 510.0 Exhaust Duct Systems > 510.9 Termination of Type I Hood Exhaust System > 510.9.1 Rooftop Terminations
503.2 Exhaust Systems, Fans
Parts of fans in contact with explosive or flammable vapors, fumes, or dusts shall be of nonferrous or nonsparking materials, or their casing shall ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 503.0 Motors, Fans, and Filters > 503.2 Fans
909.10.5 Fire Protection Systems, Fans
In addition to other requirements, belt-driven fans shall have 1.5 times the number of belts required for the design duty, with the minimum number ...
Building Code 2012 of Nevada > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.10 Equipment > 909.10.5 Fans
909.10.5 Fire Protection and Life Safety Systems, Fans
In addition to other requirements, belt-driven fans shall have 1.5 times the number of belts required for the design duty, with the minimum number ...
Building Code 2018 of Nevada > 9 Fire Protection and Life Safety Systems > 909 Smoke Control Systems > 909.10 Equipment > 909.10.5 Fans