1518.2 Underlayments
Go To Full Code Chapter
Underlayment shall be as defined in Section 1513. Underlayment shall be installed in compliance with the roofing component product approval and shall be in compliance with the following minimum requirements:
1518.2.1
Underlayment shall be attached to a nailable deck in a grid pattern of 12 inches (305 mm) between the overlaps, with 6-inch (152 mm) spacing at the overlaps.
1518.2.2
Where the architectural appearance of the underside is to be preserved, the underlayment shall be secured in accordance with Section 1519.5.2.
1518.2.3
Tin caps and nails or cap nails shall be as defined in Section 1517.5.2.
1518.2.4
Underlayment nails shall be as defined in Section 1517.5.1.
Related Code Sections
1507.1.1 Roof Assemblies and Rooftop Structures, Underlayment
Underlayment for roof slopes 2:12 and greater shall conform to the applicable standards listed in this chapter. Underlayment materials required ...
1507.1.1 Roof Assemblies and Rooftop Structures, Underlayment
Unless otherwise noted, underlayment for asphalt shingles, metal roof panels, metal roof shingles, mineral surfaced roll roofing, slate shingles ...
1507.2.3 Roof Assemblies and Rooftop Structures, Underlayment
Unless otherwise noted, required underlayment shall conform to ASTM D 226, Type I or Type II, ASTM D 4869, Type II or Type IV, or ASTM D 6757 ...
1507.3.3 Roof Assemblies and Rooftop Structures, Underlayment
Unless otherwise noted, required underlayment shall conform to: ASTM D 226, Type II, ASTM D 1970; ASTM D 2626 or ASTM D 6380, Class M mineral ...
1507.3.3 Roof Assemblies and Rooftop Structures, Underlayment
Unless otherwise noted, underlayment shall be applied according to the underlayment manufacturer's installation instructions or the recommendations ...