E4203.7 Underground Wiring
JUMP TO FULL CODE CHAPTER
Underground wiring shall not be installed under or within the area extending 5 feet (1524 mm) horizontally from the inside walls of pools and outdoor hot tubs and spas except where the wiring is installed to supply pool, spa or hot tub equipment or where space limitations prevent wiring from being routed 5 feet (1524 mm) or more horizontally from the inside walls. Where installed within 5 feet (1524 mm) of the inside walls, the wiring method shall be a complete raceway system of rigid metal conduit, intermediate metal conduit or a nonmetallic raceway system. Metal conduit shall be corrosion resistant and suitable for the location. The minimum cover depth shall be in accordance with Table E4203.7.
TABLE E4203.7
MINIMUM BURIAL DEPTHS
WIRING METHOD | UNDERGROUND WIRING (inches) |
Rigid metal conduit | 6 |
Intermediate metal conduit | 6 |
Nonmetallic raceways listed for direct burial and under concrete exterior slab not less than 4 inches in thickness and extending not less than 6 inches (162 mm) beyond the underground installation | 6 |
Nonmetallic raceways listed for direct burial without concrete encasement | 18 |
Other approved racewaysa | 18 |
For SI: 1 inch = 25.4 mm.
Related Code Sections
E4203.7 Swimming Pools [Electrical Provisions], Underground Wiring
Underground wiring shall not be installed under or within the area extending 5 feet (1524 mm) horizontally from the inside walls of pools and outdoor ...
2014 FBC - Residential, 5th edition > 42 Swimming Pools [Electrical Provisions] > E4203 Equipment Location and Clearances > E4203.7 Underground Wiring
E4203.7 Swimming Pools [Electrical Provisions], Underground Wiring
Underground wiring shall not be installed under or within the area extending 5 feet (1524 mm) horizontally from the inside walls of pools and outdoor ...
2017 FBC - Residential, 6th edition > 42 Swimming Pools [Electrical Provisions] > E4203 Equipment Location and Clearances > E4203.7 Underground Wiring
E3803.10 Wiring Methods, Wet Locations
The interior of enclosures or raceways installed underground shall be considered to be a wet location. Insulated conductors and cables installed ...
2014 FBC - Residential, 5th edition > 38 Wiring Methods > E3803 Underground Installation Requirements > E3803.10 Wet Locations
E3803.10 Wiring Methods, Wet Locations
The interior of enclosures or raceways installed underground shall be considered to be a wet location. Insulated conductors and cables installed ...
2017 FBC - Residential, 6th edition > 38 Wiring Methods > E3803 Underground Installation Requirements > E3803.10 Wet Locations
E3803.2 Wiring Methods, Warning Ribbon
Underground service conductors that are not encased in concrete and that are buried 18 inches (457 mm) or more below grade shall have their location ...
2014 FBC - Residential, 5th edition > 38 Wiring Methods > E3803 Underground Installation Requirements > E3803.2 Warning Ribbon