3406.4.5.8 Underground Tank Location
JUMP TO FULL CODE CHAPTER
Underground tanks shall be located such that the top plate thereof shall be at least 2 feet (610 mm) below the established grade. No such tank shall be buried within 10 feet (3048 mm) of any building or adjoining property line. Individual underground tanks shall be covered with 2 feet (610 mm) of earth or 4 inches (102 mm) of reinforced concrete extending 10 feet (3048 mm) beyond all the vertical walls of the tank, and the excavation made to receive the tank shall be backfilled with well-compacted clean sand or earth, free of any ash or other corrosive substance, and free from stones larger than will pass through a 1-inch (25-mm) mesh. Underground tanks may be erected in groups of 2 or more, when such tanks are separated by a space of 1 foot (305 mm), and provided the reinforced concrete top cover extends unbroken over the open space between the tanks.
Related Code Sections
G307.1 Flood-Resistant Construction, Underground Tanks
Underground tanks in areas of special flood hazard shall be designed, constructed, installed, and anchored to prevent flotation, collapse and lateral ...
G307.1 Flood-Resistant Construction, Underground Tanks
Underground tanks in areas of special flood hazard shall be designed, constructed, installed, and anchored to prevent flotation, collapse and lateral ...
Reference Standard 17 Fire, Alarms, Detection and Extinguishing Equipment [PDF] (page 13)
Reference Standard 17 distance outside of buildings. Add 3-9.2.14 Check valves on tank or pump connections, when located underground, may be placed ...
NYC 1968 Code (Vol II) [PDF] > Reference Standard 17 Fire, Alarms, Detection and Extinguishing Equipment
Reference Standard 17 Fire, Alarms, Detection and Extinguishing Equipment [PDF] (page 14)
, when located underground, may be placed inside of buildings and at a safe distance from the tank riser or pump, except in cases where the building ...
NYC 1968 Code (Vol II) [PDF] > Reference Standard 17 Fire, Alarms, Detection and Extinguishing Equipment
1305.14.1.4 Fuel-Oil Piping and Storage, External Loads on Underground Tanks
All buried storage tanks shall be constructed of at least 1 / 4 -inch-thick (6.4 mm) metal and shall be designed to withstand any external loads ...
NYC Mechanical Code 2014 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.14 Alternate Tank Design and Construction Standards > 1305.14.1 General Construction Standards > 1305.14.1.4 External Loads on Underground Tanks