// CODE SNIPPET
5704.1.2.1 Underground Flammable Liquid Tanks
Go To Full Code Chapter
Individual underground flammable liquid storage tanks shall not exceed a capacity of 4,000 gallons (15 140 L). The aggregate capacity of underground flammable liquid storage tanks at a premises shall not exceed 20,000 gallons (75 700 L).