M1601.5 Under-Floor Plenums
JUMP TO FULL CODE CHAPTER
The space shall be cleaned of loose combustible materials and scrap, and shall be tightly enclosed. The ground surface of the space shall be covered with a moisture barrier having a thickness of not less than 4 mils (0.1 mm). Plumbing waste cleanouts shall not be located within the space.
Exception: Plumbing waste cleanouts shall be permitted to be located in unvented crawl spaces that receive conditioned air in accordance with Section R408.3.
The under-floor space, including the sidewall insulation, shall be formed by materials having flame spread index values not greater than 200 when tested in accordance with ASTM E84 or UL 723.
A duct shall extend from the furnace supply outlet to not less than 6 inches (152 mm) below the combustible framing. This duct shall comply with the provisions of Section M1601.1. A noncombustible receptacle shall be installed below any floor opening into the plenum in accordance with the following requirements:
- The receptacle shall be securely suspended from the floor members and shall be not more than 18 inches (457 mm) below the floor opening.
- The area of the receptacle shall extend 3 inches (76 mm) beyond the opening on all sides.
- The perimeter of the receptacle shall have a vertical lip not less than 1 inch (25 mm) in height at the open sides.
The furnace shall be equipped with an automatic control that will start the air-circulating fan when the air in the furnace bonnet reaches a temperature not higher than 150°F (66°C). The furnace shall additionally be equipped with an approved automatic control that limits the outlet air temperature to 200°F (93°C).
Related Code Sections
M1601.5 Duct Systems, Under-Floor Plenums
Under-floor plenums shall be prohibited in new structures. Modification or repairs to under-floor plenums in existing structures shall conform ...
Residential Code 2018 of Kansas > 16 Duct Systems > M1601 Duct Construction > M1601.5 Under-Floor Plenums
R408.3 Foundations, Unvented Crawl Space
2.3. Plenum in existing structures complying with Section M1601.5, if under-floor space is used as a plenum. 2.4. Dehumidification sized to provide 70 ...
Residential Code 2018 of Kansas > 4 Foundations > R408 Under-Floor Space > R408.3 Unvented Crawl Space
Section M1601 Duct Systems, Duct Construction
Under-floor plenums shall be prohibited in new structures. Modification or repairs ...
17.7.4.2 Initiating Devices,
In under-floor spaces and above-ceiling spaces that are used as HVAC plenums, detectors shall be listed for the anticipated environment as required ...
National Fire Alarm and Signaling Code 2016 of Kansas > 17 Initiating Devices > 17.7 Smoke-Sensing Fire Detectors > 17.7.4 Heating, Ventilating, and Air-Conditioning (HVAC) > 17.7.4.2
17.7.4 Initiating Devices, Heating, Ventilating, and Air-Conditioning (HVAC)
In under-floor spaces and above-ceiling spaces that are used as HVAC plenums ...
National Fire Alarm and Signaling Code 2016 of Kansas > 17 Initiating Devices > 17.7 Smoke-Sensing Fire Detectors > 17.7.4 Heating, Ventilating, and Air-Conditioning (HVAC)