E3803.11 Under Buildings
JUMP TO FULL CODE CHAPTER
Underground cable and conductors installed under a building shall be in a raceway. [300.5(C)]
Exception: Type MC Cable shall be permitted under a building without installation in a raceway where the cable is listed and identified for direct burial or concrete encasement and one or more of the following applies:
- The metallic covering is impervious to moisture.
- A moisture-impervious jacket is provided under the metal covering.
- The insulated conductors under the metallic covering are listed for use in wet locations. [300.5(C) Exception 2]
Related Code Sections
E3803.11 Wiring Methods, Under Buildings
Underground cable and conductors installed under a building shall be in a raceway. [300.5(C)] Exception: Type MC Cable shall be permitted under ...
Residential Code 2018 of Kansas > 38 Wiring Methods > E3803 Underground Installation Requirements > E3803.11 Under Buildings
10.4.3 Underground Requirements, Private Fire Service Mains Under Buildings
Except as allowed by 10.4.3, private fire service mains shall not be allowed to run under buildings. [ 24: 10.4.3 ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 10 Underground Requirements > 10.4 Protection of Private Fire Service Mains. [24:10.4] > 10.4.3 Private Fire Service Mains Under Buildings
10.4.3.2.2 Underground Requirements,
It shall be acceptable to install the piping in covered trenches where the trenches are accessible from within the building. [ 24: 10.4.3.2.2] ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 10 Underground Requirements > 10.4 Protection of Private Fire Service Mains. [24:10.4] > 10.4.3 Private Fire Service Mains Under Buildings > 10.4.3.2* > 10.4.3.2.2
10.4.3.1.2* Underground Requirements,
Piping shall be installed a minimum of 12 in. (300 mm) below the bottom of building foundations or footers. [ 24: 10.4.3.1.2 ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 10 Underground Requirements > 10.4 Protection of Private Fire Service Mains. [24:10.4] > 10.4.3 Private Fire Service Mains Under Buildings > 10.4.3.1* > 10.4.3.1.2*
10.4.3.1.2.1 Underground Requirements,
The requirements of 10.4.3.1.2 shall not apply when the piping is sleeved with an approved material. [ 24: 10.4.3.1.2.1 ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 10 Underground Requirements > 10.4 Protection of Private Fire Service Mains. [24:10.4] > 10.4.3 Private Fire Service Mains Under Buildings > 10.4.3.1* > 10.4.3.1.2* > 10.4.3.1.2.1