Fills other than controlled fill may be considered as satisfactory bearing material of applicable class, subject to the following:
- Where spread footings will be used, the soil within the built-up area shall be explored using test pits at every column. All test pits shall extend to depths equal to the smaller width of the footing and at least one test pit shall penetrate at least 8 feet (2438 mm) below the level of the bottom of the proposed footings. All test pits shall be backfilled with properly compacted fill. Borings may be used in lieu of test pits, provided that continuous samples of at least 3 inches (76 mm) in diameter are recovered. Where mat foundations will be used, one test pit or minimum 3 inch (76 mm) diameter sampler boring shall be provided for every 1,000 square feet (232.3 m2) of building footprint area. For continuous concrete footings, one test pit or minimum 3 inch (76 mm) diameter sampler boring shall be provided for every 25 linear feet (7.62 m).
- The building area shall be additionally explored using one standard boring for every 2,500 square foot (232.3 m2) of building footprint area. These borings shall be carried to a depth sufficient to penetrate into natural ground, but not less than 20 feet (6096 mm) below grade.
- The fill shall be composed of material that is free of voids and free of extensive inclusions of mud and organic materials such as paper, wood, garbage, cans, or metallic objects and debris.
- The allowable soil bearing pressure on satisfactory uncontrolled fill material shall not exceed 2 tons per square foot (192 kPa). One and two-family dwellings may be founded on satisfactory uncontrolled fill provided the dwelling site has been explored using at least one test pit, penetrating at least 8 feet (2438 mm) below the level of the bottom of the proposed footings, and the fill has been found to be composed of material that is free of voids and generally free of mud and organic materials, such as paper, garbage, cans, or metallic objects, and debris. Test pits shall be backfilled with properly compacted fill.
Related Code Sections
1804.2.3 Soils and Foundations, Uncontrolled Fills
, wood, garbage, cans, or metallic objects, and debris. The allowable soil bearing pressure on satisfactory uncontrolled fill material shall not exceed ...
NYC Building Code 2008 > 18 Soils and Foundations > 1804 Allowable Load-Bearing Values of Soils > 1804.2 Allowable Foundation Pressure > 1804.2.3 Uncontrolled Fills
1804.2.3 Soils and Foundations, Uncontrolled Fills
pressure on satisfactory uncontrolled fill material shall not exceed 2 tons per square foot (192 kPa). One and two-family dwellings may be founded ...
NYC Building Code 2014 > 18 Soils and Foundations > 1804 Allowable Load-Bearing Values of Soils and Rock > 1804.2 Allowable Bearing Pressure > 1804.2.3 Uncontrolled Fills
1806.2.3 Soils and Foundations, Uncontrolled Fills
bearing pressure on satisfactory uncontrolled fill material shall not exceed 2 tons per square foot (191.5 kPa). One and two-family dwellings may be founded ...
NYC Building Code 2022 > 18 Soils and Foundations > 1806 Allowable Load-Bearing Values of Soils and Rock > 1806.2 Allowable Bearing Pressure > 1806.2.3 Uncontrolled Fills
1802.6.1 Soils and Foundations, Conditions Requiring Geotechnical Reports
), uncontrolled fill (see Section 1804.2.3), or artificially treated soils (see Section 1804.2.4). As required by the commissioner ...
NYC Building Code 2014 > 18 Soils and Foundations > 1802 Geotechnical Investigations and Material Classifications > 1802.6 Reports > 1802.6.1 Conditions Requiring Geotechnical Reports
Reference Standard 9 Loads [PDF] (page 13)
or Uncontrolled Fills below the ground water table, the potential for liquefaction shall be evaluated by the provisions of Section 2312(d)3. Table No. 23-K ...