506.4.2 Type II Terminations
JUMP TO FULL CODE CHAPTER
Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's installation instructions and shall comply with all of the following:
- Exhaust outlets shall terminate not less than 3 feet (914 mm) in any direction from openings into the building.
- Outlets shall terminate not less than 10 feet (3048 mm) from property lines or buildings on the same lot.
- Outlets shall terminate not less than 10 feet (3048 mm) above grade.
- Outlets that terminate above a roof shall terminate not less than 30 inches (762 mm) above the roof surface.
- Outlets shall terminate not less than 30 inches (762 mm) from exterior vertical walls.
- Outlets shall be protected against local weather conditions.
- Outlets shall not be directed onto walkways.
- Outlets shall meet the provisions for exterior wall opening protectives in accordance with the Florida Building Code, Building.
Related Code Sections
506.4.2 Exhaust Systems, Type II Terminations
Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's installation instructions and shall comply with all ...
2017 FBC - Mechanical, 6th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.4 Ducts Serving Type II Hoods > 506.4.2 Type II Terminations
506.4.2 Exhaust Systems, Type II Terminations
Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's installation instructions and shall comply with all ...
2014 FBC - Mechanical, 5th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.4 Ducts Serving Type II Hoods > 506.4.2 Type II Terminations
506.4.2 Exhaust Systems, Type II Terminations
Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's installation instructions and shall comply with all ...
2020 FBC - Mechanical, 7th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.4 Ducts Serving Type II Hoods > 506.4.2 Type II Terminations
1012.3.2 Means of Egress, Type II
Handrails with a perimeter greater than 6 1 / 4 inches (160 mm) shall provide a graspable finger recess area on both sides of the profile. The ...
2014 FBC - Building, 5th edition > 10 Means of Egress > 1012 Handrails > 1012.3 Handrail Graspability > 1012.3.2 Type II
1014.3.2 Means of Egress, Type II
Handrails with a perimeter greater than 6 1 / 4 inches (160 mm) shall provide a graspable finger recess area on both sides of the profile. The ...
2017 FBC - Building, 6th edition > 10 Means of Egress > 1014 Handrails > 1014.3 Handrail Graspability > 1014.3.2 Type II