502.6.1 Type II and III Systems
JUMP TO FULL CODE CHAPTER
Type II and III dry cleaning systems shall be provided with a mechanical ventilation system that is designed to exhaust 1 cubic foot of air per minute for each square foot of floor area (1 cfm/ft2) (0.00508 m3/(s • m2)) in dry cleaning rooms and in drying rooms. The ventilation system shall operate automatically when the dry cleaning equipment is in operation and shall have manual controls at an approved location.
Related Code Sections
502.6.1 Exhaust Systems, Type II and III Systems
Type II and III dry cleaning systems shall be provided with a mechanical ventilation system that is designed to exhaust 1 cubic foot of air per ...
NYC Mechanical Code 2014 > 5 Exhaust Systems > 502 Required Systems > 502.6 Dry Cleaning Plants > 502.6.1 Type II and III Systems
502.6.1 Exhaust Systems, Type II and Type III Systems
Type II and Type III dry cleaning systems shall be provided with a mechanical ventilation system that is designed to exhaust 1 cubic foot of air per ...
NYC Mechanical Code 2008 > 5 Exhaust Systems > 502 Required Systems > 502.6 Dry Cleaning Plants > 502.6.1 Type II and Type III Systems
1407.10 Exterior Walls, Type I, II, III and IV Construction
Where installed on buildings of Type I, II, III and IV construction, MCM systems shall comply with Sections 1407.10.1 through 1407.10.3, or Section ...
NYC Building Code 2014 > 14 Exterior Walls > 1407 Metal Composite Materials (MCM) > 1407.10 Type I, II, III and IV Construction
1407.10 Exterior Walls, Type I, II, III and IV Construction
Where installed on buildings of Type I, II, III and IV construction, MCM systems shall comply with Sections 1407.10.1 through 1407.10.4, or 1407.11 ...
NYC Building Code 2008 > 14 Exterior Walls > 1407 Metal Composite Materials (MCM) > 1407.10 Type I, II, III and IV Construction
R103.4 Acoustical Tile and Lay-In Panel Ceiling Suspension Systems, ASTM C 636, Section 2.1.5
with Section 2.1.5.1 or 2.1.5.2 as applicable. 2.1.5.1 Construction Types I and II. In buildings of Types I and II construction, hangers shall ...
NYC Building Code 2014 > R Acoustical Tile and Lay-In Panel Ceiling Suspension Systems > R103 Modifications to ASTM C 636 — Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels > R103.4 ASTM C 636, Section 2.1.5