Handrails with a circular cross section shall have an outside diameter of not less than 11/4 inches (32 mm) and not greater than 2 inches (51 mm). Where the handrail is not circular, it shall have a perimeter dimension of not less than 4 inches (102 mm) and not greater than 61/4 inches (160 mm) with a maximum cross-sectional dimension of 21/4 inches (57 mm) and minimum cross-sectional dimension of 1 inch (25 mm). Edges shall have a minimum radius of 0.01 inch (0.25 mm).

Related Code Sections

1014.3.1 Means of Egress, Type I
Handrails with a circular cross section shall have an outside diameter of not less than 11/4 inches (32 mm) and not greater than 2 inches (51 mm ...
1014.3.1 Means of Egress, Type I
Handrails with a circular cross section shall have an outside diameter of not less than 11/4 inches (32 mm) and not greater than 2 inches (51 mm ...
503.1.3 General Building Heights and Areas, Type I Construction
Buildings of Type I construction permitted to be of unlimited tabular building heights and areas are not subject to the special requirements ...
503.1.3 General Building Heights and Areas, Type I Construction
Buildings of Type I construction permitted to be of unlimited tabular building heights and areas are not subject to the special requirements ...
602.2 Types of Construction, Types I and II
Types I and II construction are those types of construction in which the building elements specified in Table 601 are of noncombustible materials ...