712.1.9 Two-Story Openings
JUMP TO FULL CODE CHAPTER
In other than Groups I-2 and I-3, a vertical opening that is not used as one of the applications listed in this section shall be permitted if the opening complies with all of the following items:
- Does not connect more than two stories.
- Does not penetrate a horizontal assembly that separates fire areas or smoke barriers that separate smoke compartments.
- Is not concealed within the construction of a wall or a floor/ceiling assembly.
- Is not open to a corridor in Group I and R occupancies.
- Is not open to a corridor on nonsprinklered floors.
- Is separated from floor openings and air transfer openings serving other floors by construction conforming to required shaft enclosures.
Related Code Sections
712.1.9 Fire and Smoke Protection Features, Two-Story Openings
if the opening complies with all of the following items: Does not connect more than two stories. Does not penetrate a horizontal assembly ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 712 Vertical Openings > 712.1 General > 712.1.9 Two-Story Openings
712.1.9 Fire and Smoke Protection Features, Two-Story Openings
if the opening complies with all of the following items: Does not connect more than two stories. Does not penetrate a horizontal assembly that separates fire ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 712 Vertical Openings > 712.1 General > 712.1.9 Two-Story Openings
404.5 Special Detailed Requirements Based on Occupancy and Use, Smoke Control
two stories when all of the following are met: 2.1. Only the two lowest stories shall be permitted to be open to the atrium ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 404 Atriums > 404.5 Smoke Control
903.2.11.1.2 Fire Protection and Life Safety Systems, Openings on One Side Only
, the story shall be equipped throughout with an approved automatic sprinkler system , or openings shall be provided on not fewer than two sides ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 903 Automatic Sprinkler Systems > 903.2 Where Required > 903.2.11 Specific Building Areas and Hazards > 903.2.11.1 Stories Without Openings > 903.2.11.1.2 Openings on One Side Only
903.2.11.1.2 Fire Protection and Life Safety Systems, Openings on One Side Only
, the story shall be equipped throughout with an approved automatic sprinkler system , or openings shall be provided on not fewer than two sides ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 903 Automatic Sprinkler Systems > 903.2 Where Required > 903.2.11 Specific Building Areas and Hazards > 903.2.11.1 Stories Without Openings > 903.2.11.1.2 Openings on One Side Only