722.2.1.2.1 Two or More Wythes
JUMP TO FULL CODE CHAPTER
The fire-resistance rating for wall panels consisting of two or more wythes shall be permitted to be determined by the formula:
(Equation 7-4)
where:
R = The fire endurance of the assembly, minutes.
R1, R2, and Rn = The fire endurances of the individual wythes, minutes. Values of Rn0.59 for use in Equation 7-4 are given in Table 722.2.1.2(1). Calculated fire-resistance ratings are shown in Table 722.2.1.2(2).
Related Code Sections
722.2.1.2.1 Fire and Smoke Protection Features, Two or More Wythes
The fire-resistance rating for wall panels consisting of two or more wythes shall be permitted to be determined by the formula: (Equation 7-4 ...
Building Code 2018 of Wyoming > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.2 Multiwythe Walls > 722.2.1.2.1 Two or More Wythes
722.2.1.2.1 Fire and Smoke Protection Features, Two or More Wythes
The fire-resistance rating for wall panels consisting of two or more wythes shall be permitted to be determined by the formula ...
Building Code 2015 of Wyoming > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.2 Multiwythe Walls > 722.2.1.2.1 Two or More Wythes
A106.3.2.1 Seismic Strengthening Provisions for Unreinforced Masonry Bearing Wall Buildings, Multiwythe Solid Brick
or horizontally. Where the backing consists of two or more wythes, the headers shall extend not less than 4 inches (102 mm) into the most distant wythe ...
Existing Building Code 2015 of Wyoming > A1 Seismic Strengthening Provisions for Unreinforced Masonry Bearing Wall Buildings > A106 Materials Requirements > A106.3 Existing Unreinforced Masonry > A106.3.2 Lay-Up of Walls > A106.3.2.1 Multiwythe Solid Brick