Distance between two hinged or pivoted doors or gates in series shall be 48 inches (1220 mm) minimum plus the width of any door or gate swinging into the space. The space between the doors and gates shall provide a turning space.
FIGURE 404.2.5(A) TWO DOORS OR GATES IN A SERIES - NEW BUILDINGS
FIGURE 404.2.5(B) TWO DOORS OR GATES IN A SERIES - NEW BUILDINGS
FIGURE 404.2.5(C) TWO DOORS OR GATES IN A SERIES - NEW BUILDINGS
The distance between two hinged or pivoted doors in series and gates in series shall be 48 inches (1220 mm) minimum plus the width of doors or gates ...