610.12.2 Tubing Systems Using Copper Fittings
JUMP TO FULL CODE CHAPTER
Maximum velocities through copper fittings in tubing other than copper shall not exceed 8 ft/s (2.4 m/s) in cold water and 5 ft/s (1.5 m/s) in hot water.
Related Code Sections
610.12.2 Water Supply and Distribution, Tubing Systems Using Copper Fittings
Maximum velocities through copper fittings in tubing other than copper shall not exceed 8 ft/s (2.4 m/s) in cold water and 5 ft/s (1.5 m/s) in hot ...
Uniform Plumbing Code 2018 of Nevada > 6 Water Supply and Distribution > 610.0 Size of Potable Water Piping > 610.12 Sizing for Velocity > 610.12.2 Tubing Systems Using Copper Fittings
G2414.10 Fuel Gas, (403.10) Metallic Piping Joints and Fittings
Copper tubing joints shall be assembled with approved gas tubing fittings, shall be brazed ...
Residential Code 2018 of Nevada > 24 Fuel Gas > G2414 (403) Piping Materials > G2414.10 (403.10) Metallic Piping Joints and Fittings
1309.4 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Brazed Joints and Fittings
Fittings shall be wrought-copper capillary fittings complying with ASME B16.22, or brazed fittings complying with ASME B16.50. Cast copper alloy ...
Uniform Plumbing Code 2018 of Nevada > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1309.0 Joints and Connections > 1309.4 Brazed Joints and Fittings
605.1 Water Supply and Distribution, Copper or Copper Alloy Pipe, Tubing, and Joints
Joining methods for copper or copper alloy pipe, tubing, and fittings shall be installed in accordance with the manufacturer's installation ...
Uniform Plumbing Code 2018 of Nevada > 6 Water Supply and Distribution > 605.0 Joints and Connections > 605.1 Copper or Copper Alloy Pipe, Tubing, and Joints
1308.5.8 Fuel Gas Piping, Metallic Piping Joints and Fittings
shall be used in systems constructed from nonferrous pipe and tubing where experience or tests have demonstrated that the joint is approved ...
Uniform Mechanical Code 2018 of Nevada > 13 Fuel Gas Piping > 1308.0 Gas Piping System Design, Materials, and Components > 1308.5 Acceptable Piping Materials and Joining Methods > 1308.5.8 Metallic Piping Joints and Fittings