5303.7.11 Tube Trailers
JUMP TO FULL CODE CHAPTER
Tube trailers, including those containing compatible compressed gases, shall be surrounded by a clear space of not less than 3 feet (914 mm) to allow for maintenance, access and inspection.
Increased separation distances between individual tube trailers containing incompatible gases shall be provided where required by Section 5303.7.1.
Piping systems used to connect tube trailers to a user piping system shall not be viewed as an encroachment into the 3-foot (914 mm) clear space.
Related Code Sections
5303.7.11 Compressed Gases, Tube Trailers
Tube trailers, including those containing compatible compressed gases, shall be surrounded by a clear space of not less than 3 feet (914 mm ...
2015 Virginia Statewide Fire Prevention Code > 53 Compressed Gases > 5303 General Requirements > 5303.7 Separation From Hazardous Conditions > 5303.7.11 Tube Trailers
5303.7.11 Compressed Gases, Tube Trailers
Tube trailers, including those containing compatible compressed gases , shall be surrounded by a clear space of not less than 3 feet (914 mm ...
2012 Virginia Statewide Fire Prevention Code > 53 Compressed Gases > 5303 General Requirements > 5303.7 Separation From Hazardous Conditions > 5303.7.11 Tube Trailers
Section 5302 Compressed Gases, Definitions
The following terms are defined in Chapter 2: COMPRESSED GAS. COMPRESSED GAS CONTAINER. COMPRESSED GAS SYSTEM. NESTING. TUBE TRAILER ...
5302.1 Compressed Gases, Definitions
The following terms are defined in Chapter 2: COMPRESSED GAS. COMPRESSED GAS CONTAINER. COMPRESSED GAS SYSTEM. NESTING. TUBE TRAILER ...
2012 Virginia Statewide Fire Prevention Code > 53 Compressed Gases > 5302 Definitions > 5302.1 Definitions