1224.33.3.7 Trauma/Cardiac Rooms
These rooms are for emergency procedures, including emergency surgery, and shall have at least 250 square feet (23.23 m2) of clear floor space. A minimum clearance of 5 feet (152 mm) shall be provided around all sides of the procedure table or gurney. Each room shall have cabinets and emergency supply shelves, image viewing capability, examination lights, and counter space for writing. Additional space with cubicle curtains for privacy may be provided to accommodate more than one patient at a time in the trauma room with a minimum clear floor area of 200 square feet (18.58 m2) for each patient bay defined by the privacy curtains. There shall be storage provided for immediate access to attire used for universal precautions. Doors leading from the ambulance entrance to the cardiac trauma room shall have an opening with a minimum width of 5 feet (1524 mm). At least one scrub sink shall be located outside the entrance to each trauma room. One scrub station consisting of two scrub positions is permitted to serve two trauma rooms if located adjacent to the entrance of each procedure room. The placement of scrub sinks shall not restrict the minimum required corridor width.