Section 1207 Transfer Fluid
JUMP TO FULL CODE CHAPTER
The flash point of transfer fluid in a hydronic piping system shall be not less than 50°F (28°C) above the maximum system operating temperature.
The transfer fluid shall be compatible with the makeup water supplied to the system.
Related Code Sections
Section 1207 Hydronic Piping, Transfer Fluid
The flash point of transfer fluid in a hydronic piping system shall be a minimum of 50°F (28°C) above the maximum system operating temperature ...
Section 1207 Hydronic Piping, Transfer Fluid
The flash point of transfer fluid in a hydronic piping system shall be not less than 50°F (28°C) above the maximum system operating temperature ...
Section 1403 Solar Systems, Heat Transfer Fluids
The flash point of the actual heat transfer fluid utilized in a solar system shall be not less than 50°F (28°C) above the design maximum nonoperating ...
Section 1403 Solar Systems, Heat Transfer Fluids
The flash point of the actual heat transfer fluid utilized in a solar system shall be not less than 50°F (28°C) above the design maximum nonoperating ...
M2301.4 Solar Energy Systems, Prohibited Heat Transfer Fluids
Flammable gases and liquids shall not be used as heat transfer fluids ...