Where the total building thermal envelope UA, the sum of U-factor times assembly area, is less than or equal to the total UA resulting from multiplying the U-factors in Table N1102.1.2 by the same assembly area as in the proposed building, the building shall be considered to be in compliance with Table N1102.1.2. The UA calculation shall be performed using a method consistent with the ASHRAE Handbook of Fundamentals and shall include the thermal bridging effects of framing materials. In addition to UA compliance, the SHGC requirements of Table N1102.1.2 and the maximum fenestration U-factors of Section N1102.5 shall be met.

Related Code Sections

N1102.1.5 [RE] Energy Efficiency, (R402.1.5) Total UA Alternative
Where the total building thermal envelope UA, the sum of U-factor times assembly area, is less than or equal to the total UA resulting from ...