2107.4 TMS 402/ACI 530/ASCE 5, Section 8.3.6, Maximum Bar Size

Go To Full Code Chapter
Add the following to Chapter 8:

8.3.6 — Maximum bar size. The bar diameter shall not exceed one-eighth of the nominal wall thickness and shall not exceed one-quarter of the least dimension of the cell, course or collar joint in which it is placed.

Related Code Sections

2107.4 Masonry, TMS 402/ACI 530/ASCE 5, Section 8.3.6, Maximum Bar Size
Add the following to Chapter 8: 8.3.6Maximum bar size. The bar diameter shall not exceed one-eighth of the nominal wall thickness and shall ...