2107.4 TMS 402/ACI 530/ASCE 5, Section 2.1.9.7, Splices of Reinforcement

Go To Full Code Chapter
Modify Section 2.1.9.7 as follows:
2.1.9.7 Splices of reinforcement. Lap splices, welded splices or mechanical splices are permitted in accordance with the provisions of this section. All welding shall conform to AWS D1.4. Welded splices shall be of ASTM A706 steel reinforcement. Reinforcement larger than No. 9 (M #29) shall be spliced using mechanical connections in accordance with Section 2.1.9.7.3.