2107.2 TMS 402/ACI 530/ASCE 5, Section 2.1.7.7.1.1, Lap Splices. I
JUMP TO FULL CODE CHAPTER
n addition to Section 2.1.7.7.1.1, it shall be permitted to design lap splices in accordance with Section 2107.2.1.
The minimum length of lap splices for reinforcing bars in tension or compression, ld, shall be
ld = 0.002db fs | (Equation 21-1) |
For SI: ld = 0.29db fs
but not less than 12 inches (305 mm). In no case shall the length of the lapped splice be less than 40 bar diameters.
where:
db | = | Diameter of reinforcement, inches (mm). |
fs | = | Computed stress in reinforcement due to design loads, psi (MPa). |
In regions of moment where the design tensile stresses in the reinforcement are greater than 80 percent of the allowable steel tension stress, Fs, the lap length of splices shall be increased not less than 50 percent of the minimum required length. Other equivalent means of stress transfer to accomplish the same 50 percent increase shall be permitted. Where epoxy coated bars are used, lap length shall be increased by 50 percent.
Related Code Sections
2107.2.1 Masonry, Lap Splices
The minimum length of lap splices for reinforcing bars in tension or compression, l d , shall be l d = 0.002 d b f s (Equation 21-1 ...
2014 FBC - Building, 5th edition > 21 Masonry > 2107 Allowable Stress Design > 2107.2 TMS 402/ACI 530/ASCE 5, Section 2.1.7.7.1.1, Lap Splices. I > 2107.2.1 Lap Splices
2107.2.1 Masonry, Lap Splices
The minimum length of lap splices for reinforcing bars in tension or compression, l d , shall be but not less than 12 inches (305 mm). In no case ...
2017 FBC - Building, 6th edition > 21 Masonry > 2107 Allowable Stress Design > 2107.2 TMS 402/ACI 530/ASCE 5, Section 8.1.6.7.1.1, Lap Splices > 2107.2.1 Lap Splices
2122.1 Masonry, Standards
unit masonry. In addition to TMS 402/ACI 530/ASCE 5 and TMS 602/ACI 530.1/ASCE 6, reinforced unit masonry structures shall comply with Sections 2122.2 ...
2014 FBC - Building, 5th edition > 21 Masonry > 2122 High-Velocity Hurricane Zones— Reinforced Unit Masonry > 2122.1 Standards
Section 2108 Masonry, Strength Design of Masonry
of TMS 402/ACI 530/ASCE 5. Where plan review and inspections are performed by a local building department in accordance with Sections 107 and 110 ...
Section 2108 Masonry, Strength Design of Masonry
of TMS 402/ACI 530/ASCE 5, except as modified by Sections 2108.2 through 2108.4. Exceptions: AAC masonry shall comply with the requirements ...