13.6.2.5.2 Three-Dimensional Fires
Go To Full Code Chapter
Large capacity dry chemical extinguishers of 10 lb (4.54 kg) or greater and having a
discharge rate of 1 lb/sec (0.45 kg/sec) or more shall be used
to protect these hazards. [10:5.5.2]