R606.4 Thickness of Masonry
JUMP TO FULL CODE CHAPTER
The minimum thickness of masonry bearing walls more than one story high shall be 8 inches (203 mm). Solid masonry walls of one-story dwellings and garages shall be not less than 6 inches (152 mm) in thickness where not greater than 9 feet (2743 mm) in height, provided that where gable construction is used, an additional 6 feet (1829 mm) is permitted to the peak of the gable. Masonry walls shall be laterally supported in either the horizontal or vertical direction at intervals as required by Section R606.6.4.
The minimum thickness of rough, random or coursed rubble stone masonry walls shall be 16 inches (406 mm).
Where walls of masonry of hollow units or masonry-bonded hollow walls are decreased in thickness, a course of solid masonry or masonry units filled with mortar or grout shall be constructed between the wall below and the thinner wall above, or special units or construction shall be used to transmit the loads from face shells or wythes above to those below.
Unreinforced solid masonry parapet walls shall be not be less than 8 inches (203203.2 mm) thick and their height shall not exceed four times their thickness. Unreinforced hollow unit masonry parapet walls shall be not less than 8 inches (203203.2 mm) thick, and their height shall not exceed three times their thickness. Masonry parapet walls in areas subject to wind loads of 30 pounds per square foot (1.44 kPa) or located in Seismic Design Category D0, D1, or D2, or on townhouses in Seismic Design Category C shall be reinforced in accordance with CRC Section R606.12.
Related Code Sections
R606.4 Wall Construction, Thickness of Masonry
The nominal thickness of masonry walls shall conform to the requirements of Sections R606.4.1 through R606.4.4 ...
Los Angeles Residential Code > 6 Wall Construction > R606 General Masonry Construction > R606.4 Thickness of Masonry
R606.4 Wall Construction, Thickness of Masonry
The nominal thickness of masonry walls shall conform to the requirements of Sections R606.4.1 through R606.4.4 ...
Los Angeles Residential Code > 6 Wall Construction > R606 General Masonry Construction > R606.4 Thickness of Masonry
R606.4.2 Wall Construction, Rubble Stone Masonry Wall
The minimum thickness of rough, random or coursed rubble stone masonry walls shall be 16 inches (406 mm) ...
Los Angeles Residential Code > 6 Wall Construction > R606 General Masonry Construction > R606.4 Thickness of Masonry > R606.4.2 Rubble Stone Masonry Wall