Thicknesses of glass panels shall be chosen either on the basis of statistical probability of breakage ( subdivision (a) of this section) or on the basis of table 10-7, at the designer's option.

(a) Statistical probability. Thickness of glass panels shall be chosen so that the statistical probability of breakage when the glass is initially subjected to the design wind load specified in table RS 9-5-1 does not exceed the values indicated in table 10-6. Probability or load factors used for design shall be derived by test. The sufficiency and validity of such test data shall be subject to approval by the commissioner.

(b) Alternate requirements. Alternative to the requirements of paragraph (a) above, the thickness of glass panels may be chosen from table 10-7. For glass with assured minimum thickness greater than required by reference standard RS 10-68, the maximum areas in table 10-7 may be increased in proportion to the assured minimum thickness.

TABLE 10-6
PROBABILITY OF BREAKAGE FOR GLASS PANELS (BASED ON COEFFICIENT OF VARIATION OF 25%)
Elevation Above Grade of
Mid-Point of Glass
Area of Panel — Sq. Ft.
-Ft 0-60 60-80 80-100 100-120 120+
0-50 1.0% 1.0% 1.0% 1.0% 1.0%
*50 or more 1.0% 0.8% 0.6% 0.4% 0.2%

*As enacted but "more than 50" probably intended.

TABLE 10-7
MAXIMUM AREA OF GLASS — SQ. FT.
Nominal Thickness of Glass-Inches Elevation Above Grade of Mid-Point of Glass-Ft.
0-50 50-300 300-600 600+
Sheet Glass
Single strength 9 9 8 7
Double strength 13 13 11 10
3/16" 25 25 21 19
7/32" 32 32 27 24
Plate and Float Glass
13/64" 25 25 21 19
1/4" 37 37 32 28
5/16" 54 54 46 40
3/8" 78 74 63 58
1/2" 114 100 86 75
5/8" 152 120 103 90
3/4" 210 137 118 103
7/8" 241 158 135 118
1" 312 204 175 153

Related Code Sections

§27-646 Structural Work, Thickness of Glass
Thicknesses of glass panels shall be chosen either on the basis of statistical probability of breakage ( subdivision (a) of this section ...
H107.2 Outdoor Signs, Glass Panels
Glass panels used in display areas of signs shall be limited in size, thickness and type of glass as provided by Table H107.2 ...
2404.3.1 Glass and Glazing, Vertical Wired Glass
= Is the wind load on the glass computed per Section 1609. Fge = Nonfactored load from ASTM E 1300 using a thickness designation ...
2404.3.1 Glass and Glazing, Vertical Wired Glass
Fge = Nonfactored load from ASTM E 1300 using a thickness designation for monolithic glass that is not greater than the thickness of wired ...
1405.11.2 Exterior Walls, Thickness
The thickness of thin exterior structural glass veneer shall be not less than 0.344 inch (8.7 mm) ...