1910.304(f)(2)(iv) The Following Additional Requirements Apply to Feeders Only:
JUMP TO FULL CODE CHAPTER
The continuous ampere rating of a fuse may not exceed three times the ampacity of the conductors. The long-time trip element setting of a breaker or the minimum trip setting of an electronically actuated fuse may not exceed six times the ampacity of the conductor. for fire pumps, conductors may be protected for short circuit only; and
Conductors tapped to a feeder may be protected by the feeder overcurrent device where that overcurrent device also protects the tap conductor.
Related Code Sections
1910.304(f)(2)(iv) Electrical, The Following Additional Requirements Apply to Feeders Only:
The continuous ampere rating of a fuse may not exceed three times the ampacity of the conductors. The long-time trip element setting of a breaker ...
OSHA 1910 General Industry > S Electrical > 1910.304 Wiring Design and Protection > 1910.304(f) Overcurrent Protection > 1910.304(f)(2) Feeders and Branch Circuits Over 600 Volts, Nominal > 1910.304(f)(2)(iv) The Following Additional Requirements Apply to Feeders Only:
1910.305(a)(2)(iv) Electrical, The Following Requirements Apply to Feeders:
) of this section, and if accessible only to qualified persons, feeders may be run as single insulated conductors ...
OSHA 1910 General Industry > S Electrical > 1910.305 Wiring Methods, Components, and Equipment for General Use > 1910.305(a) Wiring Methods > 1910.305(a)(2) Temporary Wiring > 1910.305(a)(2)(iv) The Following Requirements Apply to Feeders:
1910.304(e)(2) Electrical, Services Over 600 Volts, Nominal
The following additional requirements apply to services over 600 volts, nominal ...
OSHA 1910 General Industry > S Electrical > 1910.304 Wiring Design and Protection > 1910.304(e) Services > 1910.304(e)(2) Services Over 600 Volts, Nominal
1910.305(a)(2)(iv)(A) Electrical,
Feeders shall originate in an approved distribution center ...
OSHA 1910 General Industry > S Electrical > 1910.305 Wiring Methods, Components, and Equipment for General Use > 1910.305(a) Wiring Methods > 1910.305(a)(2) Temporary Wiring > 1910.305(a)(2)(iv) The Following Requirements Apply to Feeders: > 1910.305(a)(2)(iv)(A)
1910.261(k)(14) Special Industries, Feeder Belt
A feeder belt or other effective device shall be provided for starting paper through the calender stack ...
OSHA 1910 General Industry > R Special Industries > 1910.261 Pulp, Paper, and Paperboard Mills > 1910.261(k) Machine Room > 1910.261(k)(14) Feeder Belt