Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Sections 716.2.1.1 through 716.2.1.4 and the fire protection rating indicated in Table 716.1(2).
Exceptions:
  1. Labeled protective assemblies that conform to the requirements of this section or UL 10A, UL 14B and UL 14C for tin-clad fire door assemblies.
  2. Floor fire door assemblies in accordance with Section 712.1.13.1.
716.2.1.1 Side-Hinged or Pivoted Swinging Doors
Fire door assemblies with side-hinged and pivoted swinging doors shall be tested in accordance with NFPA 252 or UL 10C. For tests conducted in accordance with NFPA 252, the fire test shall be conducted using the positive pressure method specified in the standard.
716.2.1.2 Other Types of Assemblies
Fire door assemblies with other types of doors, including swinging elevator doors, horizontal sliding fire doors, rolling steel fire doors, fire shutters, bottom- and side-hinged chute intake doors, and top-hinged chute discharge doors, shall be tested in accordance with NFPA 252 or UL 10B. For tests conducted in accordance with NFPA 252, the neutral pressure plane in the furnace shall be maintained as nearly equal to the atmospheric pressure as possible at the top of the door, as specified in the standard.
716.2.1.3 Glazing in Transoms Lights and Sidelights in Corridors and Smoke Barriers
Glazing material in any other part of the door assembly, including transom lights and sidelights, shall be tested in accordance with NFPA 257 or UL 9, including the hose stream test, in accordance with Section 716.3.1.1.
716.2.1.4 Smoke and Draft Control
Fire door assemblies that serve as smoke and draft control assemblies shall be tested in accordance with UL 1784.

Related Code Sections

716.2.1 Fire and Smoke Protection Features, Testing Requirements
Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test ...
716.2.1 Fire and Smoke Protection Features, Testing Requirements
Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test ...
804.4.1 Interior Finishes, Test Requirement
In all occupancies, interior floor covering materials shall comply with the requirements of the DOC FF-1 "pill test" (CPSC 16 CFR Part 1630 ...
804.4.1 Interior Finishes, Test Requirement
In all occupancies, interior floor covering materials shall comply with the requirements of the DOC FF-1 "pill test" (CPSC 16 CFR Part 1630 ...