UpCodes logo
// CODE SNIPPET

Section 705 (IFGC) Testing of Hydrogen Piping Systems

Jump To Full Code Chapter
705.1 General
Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design fabrication and installation practices comply with the requirements of this code.
705.2 Inspections
Inspections shall consist of a visual examination of the entire piping system installation and a pressure test. Hydrogen piping systems shall be inspected in accordance with this code. Inspection methods such as outlined in ASME B31.12 shall be permitted where specified by the design engineer and approved by the code official. Inspections shall be conducted or verified by the code official prior to system operation.
705.3 Pressure Tests
A hydrostatic or pneumatic leak test shall be performed. Testing of hydrogen piping systems shall utilize testing procedures identified in ASME B31.12 or other approved methods, provided that the testing is performed in accordance with the minimum provisions specified in Sections 705.3.1 through 705.4.1.
705.3.1 Hydrostatic Leak Tests
The hydrostatic test pressure shall be not less than one-and-one-half times the maximum working pressure, and not less than 100 psig (689.5 kPa gauge).
705.3.2 Pneumatic Leak Tests
The pneumatic test pressure shall be not less than one-and-one-half times the maximum working pressure for systems less than 125 psig (862 kPa gauge) and not less than 5 psig (34.5 kPa gauge), whichever is greater. For working pressures at or above 125 psig (862 kPa gauge), the pneumatic test pressure shall be not less than 110 percent of the maximum working pressure.
705.3.3 Test Limits
Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
705.3.4 Test Medium
Deionized water shall be utilized to perform hydrostatic pressure testing and shall be obtained from a potable source. The medium utilized to perform pneumatic pressure testing shall be air, nitrogen, carbon dioxide or an inert gas; oxygen shall not be used.
705.3.5 Test Duration
The minimum test duration shall be 1/2 hour. The test duration shall be not less than 1/2 hour for each 500 cubic feet (14.2 m3) of pipe volume or fraction thereof. For piping systems having a volume of more than 24,000 cubic feet (680 m3), the duration of the test shall not be required to exceed 24 hours. The test pressure required in Sections 705.3.1 and 705.3.2 shall be maintained for the entire duration of the test.
705.3.6 Test Gauges
Gauges used for testing shall be as follows:
  1. Tests requiring a pressure of 10 psig (68.95 kPa gauge) or less shall utilize a testing gauge having increments of 0.10 psi (0.6895 kPa) or less.
  2. Tests requiring a pressure greater than 10 psig (68.98 kPa gauge) but less than or equal to 100 psig (689.5 kPa gauge) shall utilize a testing gauge having increments of 1 psi (6.895 kPa) or less.
  3. Tests requiring a pressure greater than 100 psig (689.5 kPa gauge) shall utilize a testing gauge having increments of 2 psi (13.79 kPa) or less.
    Exception: Measuring devices having an equivalent level of accuracy and resolution shall be permitted where specified by the design engineer and approved by the code official.
705.3.7 Test Preparation
Pipe joints, including welds, shall be left exposed for examination during the test.
705.3.7.1 Expansion Joints
Expansion joints shall be provided with temporary restraints, if required, for the additional thrust load under test.
705.3.7.2 Equipment Disconnection
Where the piping system is connected to appliances, equipment or components designed for operating pressures of less than the test pressure, such appliances, equipment and components shall be isolated from the piping system by disconnecting them and capping the outlet(s).
705.3.7.3 Equipment Isolation
Where the piping system is connected to appliances, equipment or components designed for operating pressures equal to or greater than the test pressure, such appliances, equipment and components shall be isolated from the piping system by closing the individual appliance, equipment or component shutoff valve(s).
705.4 Detection of Leaks and Defects
The piping system shall withstand the test pressure specified for the test duration specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall indicate a leak within the system. Piping systems shall not be approved except where this reduction in pressure is attributed to some other cause.
705.4.1 Corrections
Where leakage or other defects are identified, the affected portions of the piping system shall be repaired and retested.
705.5 Purging of Gaseous Hydrogen Piping Systems
Purging shall comply with Sections 705.5.1 through 705.5.4.
705.5.1 Removal From Service
Where piping is to be opened for servicing, addition or modification, the section to be worked on shall be isolated from the supply at the nearest convenient point and the line pressure vented to the outdoors. The remaining gas in this section of pipe shall be displaced with an inert gas.
705.5.2 Placing in Operation
Prior to placing the system into operation, the air in the piping system shall be displaced with inert gas. The inert gas flow shall be continued without interruption until the vented gas is free of air. The inert gas shall then be displaced with hydrogen until the vented gas is free of inert gas. The point of discharge shall not be left unattended during purging. After purging, the vent opening shall be closed.
705.5.3 Discharge of Purged Gases
The open end of piping systems being purged shall not discharge into confined spaces or areas where there are sources of ignition except where precautions are taken to perform this operation in a safe manner by ventilation of the space, control of purging rate and elimination of all hazardous conditions.
705.5.3.1 Vent Pipe Outlets for Purging
Vent pipe outlets for purging shall be located such that the inert gas and fuel gas is released outdoors and not less than 8 feet (2438 mm) above the adjacent ground level. Gases shall be discharged upward or horizontally away from adjacent walls to assist in dispersion. Vent outlets shall be located such that the gas will not be trapped by eaves or other obstructions and shall be at least 5 feet (1524 mm) from building openings and lot lines of properties that can be built on.
705.5.4 Placing Equipment in Operation
After the piping has been placed in operation, all equipment shall be purged in accordance with Section 707.2 and then placed in operation, as necessary.

Related Code Sections

Section 705 Gaseous Hydrogen Systems, (IFGC) Testing of Hydrogen Piping Systems
Inspections shall consist of a visual examination of the entire piping system installation and a pressure test. Hydrogen ...
Section 705 Gaseous Hydrogen Systems, (IFGC) Testing of Hydrogen Piping Systems
Inspections shall consist of a visual examination of the entire piping system installation and a pressure test. Hydrogen ...
Section 705 Gaseous Hydrogen Systems, (IFGC) Testing of Hydrogen Piping Systems
Inspections shall consist of a visual examination of the entire piping system installation and a pressure test. Hydrogen ...
705.4 Gaseous Hydrogen Systems, Detection of Leaks and Defects
The piping system shall withstand the test pressure specified for the test duration specified without showing any evidence of leakage or other ...
705.5 Gaseous Hydrogen Systems, Purging of Gaseous Hydrogen Piping Systems
in the piping system shall be displaced with inert gas. The inert gas flow shall be continued without interruption until the vented gas is free ...