Required emergency lighting utilizing battery powered emergency lights, exit signs, or both shall be tested annually. The emergency lights and exit signs shall be tested for proper operation for the time period established in the building code in effect when the equipment was installed. Written records of tests shall be retained by the owner of the building for a minimum of 2 years after the test is conducted and shall be made available to the fire code official upon request.

Related Code Sections

1031.10.2 Means of Egress, Power Test
Battery-powered emergency lighting equipment shall be tested annually by operating the equipment on battery power for not less than 90 minutes ...
1013.6.3 Means of Egress, Power Source
loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site ...