Special inspections shall be conducted in accordance with Section 903.1 to demonstrate compliance with the requirements of Section 807.3.1. Testing shall be conducted following the complete installation of the equipment or generators, the installation of sound reduction barriers, and balancing and operation of the equipment or generators. Testing shall be at locations representing the four cardinal directions from the face of the project building. Such testing shall demonstrate that the equipment is capable of compliance with the night-time limits under normal night-time operating conditions, and if higher sound levels are possible during the daytime, compliance with the daytime limits shall also be demonstrated.