The owner of the building or owner's authorized agent shall have the in-building, two-way emergency responder communication coverage system inspected and tested annually or where structural changes occur, including additions or remodels that could materially change the original field performance tests. Testing shall consist of the following:
  1. In-building coverage test as described in Section 510.5.4.
  2. Signal boosters shall be tested to verify that the gain is the same as it was upon initial installation and acceptance or set to optimize the performance of the system.
  3. Backup batteries and power supplies shall be tested under load of a period of 1 hour to verify that they will properly operate during an actual power outage. If within the 1-hour test period the battery exhibits symptoms of failure, the test shall be extended for additional 1-hour periods until the integrity of the battery can be determined.
  4. All active components shall be checked to verify operation within the manufacturer's specifications.
 At the conclusion of the testing, a report, which shall verify compliance with Section 510.5.4, shall be submitted to the fire code official.

Related Code Sections

510.6.1 Fire Service Features, Testing and Proof of Compliance
The owner of the building or owner's authorized agent shall have the emergency responder radio coverage system shall be inspected and tested annually ...
510.6.1 Fire Service Features, Testing and Proof of Compliance
the conclusion of the testing, a report, which shall verify compliance with Section 510.5.4, shall be submitted to the fire code official ...
3.19.1.3 Hydraulic Elevators, Component Proof Test
proof test of 5 times the component rated pressure without resulting in fracture. For elongations of less than 10%, the test value shall be 1.5 times ...
3.19.1.3 Hydraulic Elevators, Component Proof-Test
proof-test of 5 times the component rated pressure without resulting in fracture. For elongations of less than 10%, the test value shall be 1.5 times ...
715.3 Sanitary Drainage, Testing and Demonstrations
be operated to function as required by the code official and the manufacturer of the vacuum drainage system. Recorded proof of all tests shall be submitted ...