14.4.3.1*
At the request of the authority having jurisdiction, the central station facility installation shall be inspected for complete information regarding the central station system, including specifications, wiring diagrams, and floor plans that have been submitted for approval prior to installation of equipment and wiring.
14.4.3.2*
Systems and associated equipment shall be tested according to Table 14.4.3.2.
14.4.3.3
Video image smoke and flame detectors shall be inspected, tested, and maintained in accordance with the manufacturer's published instructions.
14.4.3.4
Gas detectors shall be inspected, tested, and maintained in accordance with manufacturer's published instructions.
14.4.3.5 Testing of CO System Detectors
For all carbon monoxide system detectors installed after January 1, 2012, carbon monoxide tests shall be performed at initial acceptance and annually by the introduction of carbon monoxide into the sensing chamber or element.