Cables entering enclosures that are required to be explosionproof shall be sealed at the point of entrance. The sealing fitting shall comply with 501.15(B)(1) or be explosionproof. Multiconductor or optical multifiber cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core that are installed in a Division 2 location shall be sealed with a listed fitting after the jacket and any other coverings have been removed, so that the sealing compound can surround each individual insulated conductor or optical fiber tube in such a manner as to minimize the passage of gases and vapors. Multiconductor or optical multifiber cables installed in conduit shall be sealed as described in 501.15(D).
Exception No. 1: Cables leaving an enclosure or room that is unclassified as a result of Type Z pressurization and entering into a Division 2 location shall not require a seal at the boundary.
Exception No. 2: Shielded cables and twisted pair cables shall not require the removal of the shielding material or separation of the twisted pairs, provided the termination is by an approved means to minimize the entrance of gases or vapors and prevent propagation of flame into the cable core.

Related Code Sections

1023.3 Means of Egress, Termination
Interior exit stairways and ramps shall terminate at an exit discharge or a public way. Exception: A combination of interior exit stairways ...
1023.3 Means of Egress, Termination
Interior exit stairways and ramps shall terminate at an exit discharge or a public way. Exception: A combination of interior exit stairways ...
1024.4 Means of Egress, Termination
Exit passageways on the level of exit discharge shall terminate at an exit discharge. Exit passageways on other levels shall terminate at an exit ...
1024.4 Means of Egress, Termination
Exit passageways on the level of exit discharge shall terminate at an exit discharge. Exit passageways on other levels shall terminate at an exit ...
(A) General, Terminals
Connection of conductors to terminal parts shall ensure a thoroughly good connection without damaging the conductors and shall be made by means ...