5.504.1 Temporary Ventilation
JUMP TO FULL CODE CHAPTER
The permanent HVAC system shall only be used during construction if necessary to condition the building or areas of addition or alteration within the required temperature range for material and equipment installation. If the HVAC system is used during construction, use return air filters with a Minimum Efficiency Reporting Value (MERV) of 8, based on ASHRAE 52.2-1999, or an average efficiency of 30 percent based on ASHRAE 52.1-1992. Replace all filters immediately prior to occupancy, or, if the building is occupied during alteration, at the conclusion of construction.
Related Code Sections
5.504.1 Nonresidential Mandatory Measures, Temporary Ventilation
The permanent HVAC system shall only be used during construction if necessary to condition the building or areas of addition or alteration within ...
California Green Building Standards Code 2019 > 5 Nonresidential Mandatory Measures > 5.504 Pollutant Control > 5.504.1 Temporary Ventilation
5.504.1 Nonresidential Mandatory Measures, Temporary Ventilation
The permanent HVAC system shall only be used during construction if necessary to condition the building or areas of addition or alteration within ...
California Green Building Standards Code 2016 > 5 Nonresidential Mandatory Measures > 5.504 Pollutant Control > 5.504.1 Temporary Ventilation
5.504.1 Nonresidential Mandatory Measures, Temporary Ventilation
The permanent HVAC system shall only be used during construction if necessary to condition the building or areas of addition or alteration within ...
California Green Building Standards Code 2022 > 5 Nonresidential Mandatory Measures > 5.504 Pollutant Control > 5.504.1 Temporary Ventilation
A5.504.1.1 Nonresidential Voluntary Measures, Temporary Ventilation
Provide temporary ventilation during construction in accordance with Section 120.1 (Requirements for Ventilation) of the California Energy Code ...
California Green Building Standards Code 2016 > A5 Nonresidential Voluntary Measures > A5.504 Pollutant Control > A5.504.1 Indoor Air Quality (IAQ) During Construction > A5.504.1.1 Temporary Ventilation
A5.504.1.1 Nonresidential Voluntary Measures, Temporary Ventilation
Provide temporary ventilation during construction in accordance with Section 120.1 (Requirements for Ventilation) of the California Energy Code ...
California Green Building Standards Code 2019 > A5 Nonresidential Voluntary Measures > A5.504 Pollutant Control > A5.504.1 Indoor Air Quality (IAQ) During Construction > A5.504.1.1 Temporary Ventilation