16.5.2 Temporary Separation Walls
Go To Full Code Chapter
16.5.2.1
Protection shall be provided to separate an occupied portion of the structure from a portion of the structure undergoing alteration, construction, or demolition operations when such operations are considered as having a higher level of hazard than the occupied portion of the building. [241:8.6.2.1]
16.5.2.1.1
Walls shall have at least a 1-hour fire resistance rating. [241:8.6.2.1.1]
16.5.2.1.2
Opening protectives shall have at least a 45-minute fire protection rating. [241:8.6.2.1.2]
16.5.2.2*
Walls in 16.5.2.1.1 and opening protectives in 16.5.2.1.2 shall be permitted to be nonrated when an approved automatic sprinkler system is installed and operational. [241:8.6.2.2]
Related Code Sections
16.4.2 Safeguarding Construction, Alteration, and Demolition Operations, Temporary Separation Walls
Protection shall be provided to separate an occupied portion of the structure from a portion of the structure undergoing alteration, construction ...
16.5.2 Safeguarding Construction, Alteration, and Demolition Operations, Temporary Separation Walls
Protection shall be provided to separate an occupied portion of the structure from a portion of the structure undergoing alteration, construction ...
16.5.2.1 Safeguarding Construction, Alteration, and Demolition Operations,
Protection shall be provided to separate an occupied portion of the structure from a portion of the structure undergoing alteration, construction ...
16.4.2.3 Safeguarding Construction, Alteration, and Demolition Operations,
Opening protectives shall have at least a 45-minute fire protection rating. [241:8.6.2.3 ...
16.5.2.1.2 Safeguarding Construction, Alteration, and Demolition Operations,
Opening protectives shall have at least a 45-minute fire protection rating. [241:8.6.2.1.2 ...