3303.7.7.4 Temporary Protection of Structural Connections
Go To Full Code Chapter
Where a structural connection
between a girder and column is not provided with its permanent fire-rated enclosure or
protection, it shall be protected by a temporary 1-hour rated enclosure or protection. Such
temporary enclosure or protection shall be installed as soon as practical after the connection
has been made, and no later than by the end of the shift.