3303.2.3.1 Temporary Lighting for Construction Sites
JUMP TO FULL CODE CHAPTER
Temporary lighting for construction sites shall use high-efficacy lamps with the following minimum efficacies:
- 60 lumens per watt for lamps over 40 watts;
- 50 lumens per watt for lamps over 15 watts but less than or equal to 40 watts; and
- 40 lumens per watt for lamps 15 watts or less.
Related Code Sections
3303.2.3.1 Safeguards During Construction or Demolition, Temporary Lighting for Construction Sites
Temporary lighting for construction sites shall use high-efficacy lamps with the following minimum efficacies: 60 lumens per watt for lamps over 40 ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3303 Safeguards and Maintenance of Site > 3303.2 Utilities > 3303.2.3 Electrical Work > 3303.2.3.1 Temporary Lighting for Construction Sites
3303.2.3.1 Safeguards During Construction or Demolition, Temporary Lighting for Construction Sites
Temporary lighting for construction sites shall use high-efficacy lamps with the following minimum efficacies: 60 lumens per watt for lamps over 40 ...
NYC Building Code 2022 > 33 Safeguards During Construction or Demolition > 3303 Safeguards and Maintenance of Site > 3303.2 Utilities > 3303.2.3 Electrical Work > 3303.2.3.1 Temporary Lighting for Construction Sites
*3301.13.7 Safeguards During Construction or Demolition, Duties of Construction Superintendents
The duties of a construction
superintendent shall include:
Acting in a reasonable and responsible manner to maintain a safe job site and assure ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3301 General > *3301.13 Scope > *3301.13.7 Duties of Construction Superintendents
*3301.13.7 Safeguards During Construction or Demolition, Duties of Construction Superintendents
of concrete floors;
Work limited to providing the site with temporary heat, light, or water; or
Truck deliveries to the site, provided the delivery occurs ...
NYC Building Code 2022 > 33 Safeguards During Construction or Demolition > 3301 General > *3301.13 Scope > *3301.13.7 Duties of Construction Superintendents
3303.11.1 Safeguards During Construction or Demolition, Temporary Stairways in Unoccupied Buildings
exceeding 50 feet (15 240 mm) in height is altered, at least one temporary lighted stairway shall be provided, unless one or more of the permanent stairways ...
NYC Building Code 2008 > 33 Safeguards During Construction or Demolition > 3303 Safeguards and Maintenance of Site > 3303.11 Maintenance of Exits During Construction or Demolition > 3303.11.1 Temporary Stairways in Unoccupied Buildings