16.2.1.1*
Temporary heating equipment shall be listed. [241:5.2.1]
16.2.1.2
Temporary heating equipment shall be installed in accordance with its listing, including clearance to combustible material, equipment, or construction. [241:5.2.2]
16.2.1.3
Temporary heating equipment shall be installed, used, and maintained in accordance with the manufacturer's instructions, except as otherwise provided in 16.2.1.4. [241:5.2.3]
16.2.1.4
Where instructions, as addressed in 16.2.1.3, are not available, temporary heating equipment shall be used in accordance with recognized safe practices. [241:5.2.4]
16.2.1.5
Temporary heating equipment shall be situated so that it is secured. [241:5.2.5]
16.2.1.6
Only personnel familiar with the operation of the temporary heating equipment shall be allowed to operate such devices. [241:5.2.6]
16.2.1.7*
Temporary heating equipment, where utilized, shall be monitored for safe operation and maintained by properly trained personnel. [241:5.2.7]
16.2.1.8
Temporary heating equipment and devices noted to be damaged or considered to be a potential safety hazard shall not be used. [241:5.2.8]
16.2.1.9
Temporary heating equipment using exposed radiant heating wires shall not be used. [241:5.2.9]
16.2.1.10
Temporary electrical heating equipment shall be equipped with tip-over protection and overheat cutoffs. [241:5.2.10]
16.2.1.11
Chimney or vent connectors, where required from direct-fired heaters, shall be maintained at least 18 in. (460 mm) from combustibles and shall be installed in accordance with NFPA 211. [241:5.2.11]
16.2.1.12
Oil-fired heaters shall comply in design and installation features with Section 11.5. [241:5.2.12]
16.2.1.13
Fuel supplies for liquefied petroleum gas-fired heaters shall comply with NFPA 54 and Chapter 69. [241:5.2.13]
16.2.1.14
Refueling operations shall be conducted in an approved manner. [241:5.2.14]