Tempered water shall be controlled by one the following:
  1. A limiting device conforming to ASSE 1070/ASME A112.1070/CSA B125.70 and set to not greater than 110°F (43°C).
  2. A thermostatic mixing valve conforming to ASSE 1017.
  3. A water heater conforming to ASSE 1082.
  4. A water heater conforming to ASSE 1084.
This provision shall not supersede the requirement for protective shower valves in accordance with Section 412.3.

Related Code Sections

607.1.2 Water Supply and Distribution, Tempered Water Temperature Control
Tempered water shall be supplied through a water temperature limiting device that conforms to ASSE 1070 and shall limit the tempered water ...
C404.7 [CE] Commercial Energy Efficiency, Demand Recirculation Controls
or sensing the flow of hot or tempered water to a fixture fitting or appliance. The control shall limit the temperature of the water entering the cold ...