An approved temperature relief valve shall be installed on all equipment used for heating or storing hot water and which forms part of a water supply system. When the temperature of the water within the vessel to which such relief valve is connected reaches 210oF, the valve shall automatically discharge sufficient hot water to prevent any further rise in the temperature. Each temperature relief valve shall be rated in terms of the maximum permissible hourly BTU input which the valve can safely relieve, and such rating shall be plainly stamped, etched, or cast on the valve or on a permanent nameplate securely attached to the valve. Temperature relief valves shall be installed in the hot water connection to the heater or storage tank in such a manner that the stem of the temperature-sensing element will project at least one inch into the tank.

Related Code Sections

P-812.2 Water Supply and Distribution, Temperature Relief
An approved temperature relief valve shall be installed on all equipment used for heating or storing hot water and which forms part of a water supply ...
P2804.4 Water Heaters, Temperature Relief Valves
Temperature relief valves shall have a relief rating compatible with the temperature conditions of the appliances or equipment protected. The valves ...
504.4 Water Heaters, Relief Valve
and temperature relief valve or combination thereof. The relief valve shall conform to ANSI Z21.22. The relief valve shall not be used as a means ...