Except as provided for in Section P2904.2.2, sprinklers shall have a temperature rating of not less than 135°F (57°C) and not more than 225°F (107°C). Sprinklers shall be separated from heat sources as required by the sprinkler manufacturer's installation instructions.

Related Code Sections

8.3.2 Installation Requirements, Temperature Ratings
Based on Distance from Heat Sources Type of Heat Condition Ordinary-Temperature Rating Intermediate-Temperature Rating High-Temperature ...
8.3.2 Installation Requirements, Temperature Ratings
Ratings of Sprinklers Based on Distance from Heat Sources Type of Heat Condition Ordinary-Temperature Rating Intermediate-Temperature Rating ...
9.4.2 Sprinkler Location Requirements, Temperature Ratings
) Temperature Ratings of Sprinklers in Specified Residential Areas Heat Source Minimum Distance from Edge of Source to Ordinary-Temperature ...