Floor furnaces shall be provided with temperature limit controls in accordance with the following requirements:
  1. Listed automatically operated floor furnaces shall be equipped with temperature limit controls. [NFPA 54:10.11.2.1]
  2. Unlisted automatically operated floor furnaces shall be equipped with a temperature limit control arranged to shut off the flow of gas to the burner in the event the temperature at the warm air outlet register exceeds 350°F (177°C) above room temperature. [NFPA 54:10.11.2.2]

Related Code Sections

906.2 Installation of Specific Appliances, Temperature Limit Controls
Floor furnaces shall be provided with temperature limit controls in accordance with the following requirements: Listed automatically operated ...
490.73 Equipment for General Use, Pressure and Temperature Limit Control
Each boiler shall be equipped with a means to limit the maximum temperature, pressure, or both, by directly or indirectly interrupting all current ...
607.7 Duct Systems, Temperature Limit
A furnace supplying warm air to such space shall be equipped with an approved temperature limit control that will limit outlet air temperature to 200 ...
306.0 General Regulations, Automatic Control Devices
with a listed air outlet temperature limit control that cannot be set for temperatures exceeding 250°F (121°C). Such controls shall be located ...