Section 613 Temperature Control Devices and Valves

Go To Full Code Chapter
613.1 Temperature-Actuated Mixing Valves
Temperature-actuated mixing valves, which are installed to reduce water temperatures to defined limits, shall comply with ASSE 1017. Such valves shall be installed at the hot water source.